SIN-00183701 Renewal 02/23/2021 Compliant - Finalized
RegulationLIS Non-Compliance AreaCorrection RequiredPlans of CorrectionCorrection DatePOC Status
6400.68(b)At the time of the inspection the water temperature in the bathroom registered 123.6F. Hot water temperatures in bathtubs and showers may not exceed 120°F. The temperature of the water heater was lowered. The water temperature was tested three times and did not exceed 120°F. Water temperatures will be checked monthly on the 1st of each month by maintenance to protect the individual from accidental scalding. 03/02/2021 Implemented
6400.101At the time of inspection the back door leading outside did not open.Stairways, halls, doorways, passageways and exits from rooms and from the building shall be unobstructed. The door was repaired right after the time of inspection and staff had no issues with opening and closing the door. Sunset CEO, or whom he designates this responsibility to, will be conducting monthly house checks using the Regulatory Compliance Guide to ensure that all exits from the building are not obstructed. 03/02/2021 Implemented
SIN-00218931 Renewal 02/13/2023 Compliant - Finalized