Inspection IDReason for InspectionInspection DateInspection Status 
SIN-00185596 Renewal 03/03/2021 Compliant - Finalized
RegulationLIS Non-Compliance AreaCorrection RequiredPlans of CorrectionCorrection DatePOC Status
6400.68(b)The Hot water temperatures in bathtubs / shower exceeded 120°F, it read 124.5°F Hot water temperatures in bathtubs and showers may not exceed 120°F. The water temperature at this Site was lowered to about 102°F on 03/03/2021 by maintenance. Please see attachment #11. 03/03/2021 Implemented
6400.82(e)The bathroom tub did not contain a nonslip surface or a mat. Bathtubs and showers shall have a nonslip surface or mat. A no-slip mat was situated in the bathroom tub as of 03/03/2021. Please see attachment #12. 03/03/2021 Implemented
6400.111(a)There was no operable fire extinguisher located in the basement.There shall be at least one operable fire extinguisher with a minimum 2-A rating for each floor, including the basement and attic. The fire extinguisher for the basement, which was originally placed in the steps leading right into the basement, was moved into the basement on 03/03/2021. Please see attachment #13. 03/03/2021 Implemented
6400.111(f)The fire extinguisher located in the kitchen was not inspected by a Fire Safety Expert, there was no inspection tag on the fire extinguisher. A fire extinguisher shall be inspected and approved annually by a fire safety expert. The date of the inspection shall be on the extinguisher. The fire extinguisher was inspected in November 2020 but the tag was missing at the time of the inspection. The inspection tag for this fire extinguisher was replaced on 03/03/2021. Please see attachment #14. 03/03/2021 Implemented