Inspection IDReason for InspectionInspection DateInspection Status 
SIN-00199741 Renewal 01/31/2022 Compliant - Finalized
RegulationLIS Non-Compliance AreaCorrection RequiredPlans of CorrectionCorrection DatePOC Status
6400.68(a)The home did not have adequate hot water under pressure. The water temperature in the bathtub was 92.7 degrees.A home shall have hot and cold running water under pressure. A work order was submitted the date of inspection and the issue was resolved by replacing the scald guard the next day. Water is now registering at an acceptable temperature. 04/01/2022 Implemented
6400.73(a)There is no handrail on the steps leading out of the basement of the home. Each ramp, and interior stairway and outside steps exceeding two steps shall have a well-secured handrail. A work order was submitted to maintenance on the day of inspection. Handrail will be installed. This was a new development site. Regulation will be reviewed with Facilities Maintenance Coordinator. 04/01/2022 Implemented
SIN-00237646 Renewal 01/23/2024 Compliant - Finalized
SIN-00183606 Renewal 02/23/2021 Compliant - Finalized