Inspection IDReason for InspectionInspection DateInspection Status 
SIN-00227248 Renewal 07/06/2023 Compliant - Finalized
RegulationLIS Non-Compliance AreaCorrection RequiredPlans of CorrectionCorrection DatePOC Status
6400.110(b)The nearest smoke detector was 18 feet 4 inches from the bedroom door of Individual #1 and 18 feet and 3 inches from the bedroom door of Individual #2 and 18 feet and 3 inches from the bedroom door of Individual #3.There shall be an operable automatic smoke detector located within 15 feet of each individual and staff bedroom door. Immediate corrective plan ¿ Additional Detectors were added to common area at Dell Way (pictures attached). Responsible Party Rick Petro, Maintenance Director ¿ completed July 7, 2023. All other sites were checked and measured between July 20th and July 24th and were determined to be compliant. Responsible Party Jason McIntosh, CAO 07/07/2023 Implemented
SIN-00176006 Renewal 09/10/2020 Compliant - Finalized
SIN-00134633 Renewal 05/08/2018 Compliant - Finalized
SIN-00041257 Renewal 10/31/2012 Compliant - Finalized